Features:

  • True double-conversion online UPS
  • Smart battery charger design to optimize battery performance
  • Output power factor 1.0
  • Wide input voltage range (110 V -300 V)
  • 50/60 Hz Frequency Converter Mode
  • ECO mode operation for energy saving
  • Built in isolation transformer (Option)
  • Emergency Power Off (EPO) Function
  • USB+RS232
  • SNMP Optional



Where to buy Compare

MODEL

Premium II 10K (L)

CAPACITY

10000 VA /10000 W

INPUT

Nominal Voltage 208/220/230/240 VAC
Voltage Range 110-300 VAC at 50% load
176-300 VAC at 100% load
Frequency Range 46 ~ 54 Hz or 56 ~ 64 Hz
Power Factor 0.99 @ 100% Load

OUTPUT

Output Voltage 208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Synchronized Range) 46 ~ 54 Hz or 56 ~ 64 Hz
Current Crest Ratio 3:1
Harmonic Distortion 3 % THD (Linear Load)
6 % THD (Nonlinear Load)
Transfer Time AC Mode to Batt. Mode:Zero
Inverter to Bypass:Zero

EFFICIENCY

AC Mode 89%
Battery Mode 88%

BATTERY Standard Model

Battery Type 12 V / 9 Ah
Numbers 20
Typical Recharge Time 9 hours recover to 90% capacity
Charging Current (max.) 1.0 A
Charging Voltage 273.0 VDC ±1%

BATTERY Long-run Model

Battery Type Depending on applications
Numbers 18-20
Charging Current (max.) 4.0 A
Charging Voltage 273.0 VDC ±1%

PHYSICAL Standard Model

Dimension, D X W X H (mm) 592 x 250 x 576
Net Weight (kgs) 83

PHYSICAL Long Run Model

Dimension, D X W X H (mm) 592 x 250 x 576
Net Weight (kgs) 27

OPERATING ENVIRONMENT

Humidity 20-90 % RH @ 0-40°C (Non-condensing)
Noise Level Less than 58dB@1Meter

MANAGEMENT

Smart RS-232 Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser