In compare 0 items

Cells Per Unit 6
Voltage Per Unit 12
Nominal Capacity 12.2Ah@20hour-rate to 1.75V per cell @25?
Weight Approx. 3.30 Kg (Tolerance±4.0%)
Internal Resistance Approx. 16.5 mO
Terminal F1/F2
Max. Discharge Current 120A (5 sec)
Short Circuit Current 570A
Design Life 6~8 years (Float charging)
Recommended Maximum Charging Current 3.6 A
Reference Capacity C3 9.31AH
C5 10.5AH
C10 11.3AH
C20 12.1AH
Standby Use Voltage
13.7 V ~ 13.9 V @ 25?
Temperature Compensation: -3mV/C/Cell
Cycle Use Voltage
14.6 V~14.8 V @ 25C
Temperature Compensation: -4mV/C/Cell
Operating Temperature Range Discharge: -20?~60C
Charge: 0C ~50C
Storage: -20C~60C
Normal Operating Temperature Range 25C±5C
Self Discharge Crown Valve Regulated Lead Acid (VRLA) batteries can
be stored for up to 6 months at 25? and then recharging
is recommended. Monthly Self-discharge ratio is less
than 3% at 25?.Please charge batteries before using.
Container Material A.B.S. UL94-HB, UL94-V0 Optional.